GENERATING SET
Fully compatible with electric generators.
The Innova UPS PLUS Range is a double conversion On Line range with VFI certification (Voltage and Frequency
Independent), which due to its characteristics makes it the ideal equipment to protect critical installations from
your company (CPD, PLC, servers, etc.).
It is a range with the possibility of mounting in a parallel and/or parallel redundant arrangement, as well as admitting
Expansion in autonomy in a simple way according to your needs and requirements.
It also has an intelligent battery charging system (SENSICHARGER), which, depending on a series of
operating and environmental parameters with which the machine is working, carry out the load to obtain
maintain an optimal state of recharge and increase their average life.
ENTRANCES AND PORTS
- USB port
– RS232 port
– RS485 port
– SNMP card slot
– Slot for dry contact relay card
TYPICAL APPLICATIONS
– Automated doors
– Mini CPD
– Access control and barriers
– Hospitals
– Administration buildings
- Schools
- Industrial automation
- Industrial
– Telecommunications
- Transportation
FEATURES
– SENSICHARGER battery charging system
- Management software
– Emergency EPO system
– High frequency IGBT technology
– THDI <3%
– Possibility of extended autonomy
– Potential growth potential
using the N+1 positioning system
in parallel
MODEL | PLUS 1000 | PLUS 2000 | PLUS 3000 |
Capacity | 1000VA / 900W | 2000VA / 1800W | 3000VA / 2700W |
STARTERS | |||
Phase | Phase+Ground | ||
Tensions | 200/208/220/230/240 VAC | ||
Voltage range |
110-290V |
||
Frequency |
45Hz~65Hz (Auto adjustable) |
||
Power factor |
> 0,98 |
||
THDi |
< 7% (100% non-linear load) |
||
Bypass voltage range |
Max. Voltage: +15% (optional +5%, +10%, +25%) Min. Voltage: –45% (optional -20%, -30%) Frequency range: ±10% |
||
range in ECO mode |
same as bypass |
||
group entry |
Admits |
||
PROJECTION | |||
Phase |
Phase+Ground | ||
Tensions | 200/208/220/230/240VAC | ||
Power factor | 0.9 | ||
Voltage Regulation | ± 2% | ||
crest factor | 3:1 | ||
Frequency | Normal mode 50Hz or 60Hz (synchronized with the main network)
Battery mode 50/60Hz±0.02Hz |
||
THD | ≤3% with linear load ≤5% with non-linear load | ||
Waveform | Pure Sine | ||
EFFICIENCY | |||
AC mode (full charge) | up to 88% | up to 89% | |
ECO mode (full charge) | >94% | ||
DRUMS | |||
Tension | 24Vdc | 48Vdc | 72Vdc |
Capacity (standard model) | 9AH | ||
Autonomy time | Full charge <5 min., Estimated runtime remaining visible on LCD | ||
Capacity (standard model) | 9AH | ||
Autonomy time | Full charge >5 min., Estimated remaining battery life visible on LCD | ||
90% recharge time | 5 hours | ||
Charging current | 1A | ||
TRANSFER TIME | |||
normal battery | 0ms | ||
normal to bypass | <4ms | ||
PROTECTION | |||
Overload | Load≤100%-150%: for 30s, ≥150%: for 300ms Immediate power off | ||
Short circuit | maintains the system | ||
Overheating | Line Mode: Transfer to Bypass; Battery Mode: Direct Power Off | ||
Low battery | alarm and shutdown | ||
Self-diagnosis | At power on and through Software | ||
EPO (optional) | Immediate UPS shutdown | ||
Battery | Advanced Battery Management | ||
noise suppression | Conforms to EN62040-2 | ||
ALARMS | |||
Audible & Visual | Line Fail, Low Battery, Overload, System Failure | ||
DISPLAY | |||
LED & LCD status | Line Mode, Backup Mode, Eco Mode, Bypass Mode, Low Battery, Bad Battery, Overload and System Fault | ||
Visual on LCD | Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load Percentage, Battery Voltage. | ||
PHYSICAL CHARACTERISTICS | |||
Dimensions (WxHxD) mm | 140x215x90 | 390x145x210 | 466x190x330 |
Weight (kg) | 13 | 21,6 | 27 |
input connection | IEC320-C14-10A | IEC320-C20-16A | IEC320-C20-16A |
output connection | IEC320-C13-10A x 3 | IEC C13-10A x 8 | IEC320-C13-10A x 8 & C19-16A x 1 |
External battery connection | Anderson type internal connection | ||
COMMUNICATION INTERFACE | |||
Smart RS232/USB ports | Support Windows Family, Linux, FressDSB, etc. | ||
ENVIRONMENTAL CHARACTERISTICS | |||
Operating temperature | 0ºC ~ 40ºC | ||
Storage temperature | -25ºC ~ + 55ºC | ||
Humidity | 0~95% non-condensing | ||
Altitude | < 1500m (with losses when > 1500m) | ||
Noise | <50dB (at 1 meter) | ||
SAFETY RULES CE,CB | |||
IEC/EN62040-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC1000-4-8. |
Reviews
Not yet reviewed