INEO RT is a last generation double conversion On Line equipment, convertible. The INEO RT Range is designed with DSP control, with a high power factor, both at input and output (Cosine of Phi=1), wide input voltage range to achieve energy savings, and the ECOMODE system, which make it one of the most efficient on the market.
It is the ideal equipment for server rooms, banks, industrial equipment, IT equipment, communication systems and other networking equipment, which demand superior protection.
ENTRANCES AND PORTS
- USB port
– RS232 port
– RS485 port
– SNMP card slot
– Slot for dry contact relay card
FORMAT
Convertible to tower or rack mount format
19" cabinets.
GENERATING SET
Fully compatible with electric generators
TYPICAL APPLICATIONS
– Automated doors
– Great CPD
– Access control and barriers
– Hospitals
– Administration buildings
- Schools
- Industrial automation
- Industrial
– Telecommunications
- Transportation
– SENSICHARGER battery charging system
– Multifunction LCD display
– Emergency EPO system
– Wide input voltage range
– Possibility of extended autonomy
– Potential growth potential
using the N+1 positioning system
in parallel
MODEL | INEO RT1000 | INEO RT2000 | INEO RT3000 |
Capacity | 1000VA/1000W | 2000VA/2000W | 3000VA/3000W |
STARTERS |
|||
Phase | Phase + Neutral | ||
Voltage range | 200 / 208 / 220 / 230 / 240VAC | ||
Voltage range | Low line transfer 160Vac±5% @ 100% ~ 80% load; 140Vac±5% @ 80% ~ 70% load; 120Vac±5%@ 70% ~ 60% load; 110Vac ±5%@ 60% ~ 0% (Ambient Temp. <35ºC)Minimum line return 175Vac ± 5% @ 100% ~ 80% load; 155Vac± 5% @ 80% ~70% load; 135Vac± 5%@ 60% ~ 0% load; (Ambient Temp. <35ºC) Transfer by maximum 300Vac ± 5%Return due to maximum voltage 290Vac ± 5% |
||
Frequency range | 40Hz-70Hz (auto detectable) |
||
Power factor | 0.99 ≥ | ||
Bypass voltage range | Maximum voltage point 230 ~ 264 Adjustable the maximum voltage point on LCD from 230Vac to 264Vac (Default : 264Vac)
Minimum voltage point 270 ~ 220 LCD minimum voltage point setting from 170Vac to 220Vac (Default : 170Vac) |
||
ECHO range | same as bypass | ||
group entry | Admits |
||
PROJECTION | |||
Phase | Phase + Neutral | ||
Rated voltage |
200 / 208 / 220 / 230 / 240VAC | ||
Power factor |
1 | ||
voltage regulation |
± 1% | ||
Frequency | Normal mode 47 ~ 53Hz (for 50Hz) or 57 ~ 63Hz (for 60Hz)
Battery mode 50 / 60Hz ±0.01Hz |
||
crest factor |
3:1 | ||
THDv | ≤ 3% with linear load ≤ 6% with non-linear load |
||
Waveform | pure sine | ||
EFFICIENCY |
|||
AC mode (full load) |
> 88% | <92% | <92% |
BATTERY | |||
Autonomy | Typical: For models with long autonomy depending on the load |
||
90% recharge time | 4 hours |
||
Charging current | 1A |
||
TRANSFER TIME |
|||
battery mains | WHO | ||
network to bypass | <4 ms | ||
PROTECTION |
|||
Over load AC mode | 35ºC < Ambient Temp. <35ºC 105%~110%: UPS transfers to bypass after 10 minutes of mains normal. 110%~130%: UPS transfers to bypass after 1 minute when mains is normal. 130%~150%: UPS transfers to bypass after 5 seconds when mains is normal. >150%: UPS transfers to bypass immediately when mains is normal |
||
Over charge Battery mode | 35ºC < Ambient Temp. <40ºC 105%~110%: UPS transfer to bypass after 1 minute when mains is normal 110%~130%: UPS transfer to bypass after 5 seconds when mains is normal >130%: UPS transfers to bypass immediately |
||
Over load bypass mode | 10A (Input fuse) | 16A (Input Fuse) | 20A (Input Fuse) |
Short circuit | maintains the system | ||
Overheating | line mode; switch to bypass; backup mode; turn off the UPS immediately | ||
Battery |
alarm and shutdown |
||
EPO (optional) | UPS Shutdown Immediately | ||
Low battery | Advanced battery management | ||
ALARMS | |||
audible and visual | Line fault, low battery, overload, system fault |
||
DISPLAY | |||
Status LED and LCD | Line mode, backup mode, ECO mode, bypass mode, low battery, bad battery, overload and UPS failure |
||
LCD reading | Input voltage, input frequency, output voltage, output frequency, load percentage, input voltage battery |
||
PHYSICAL |
|||
Dimensions |
× × 440 86,5 305 | × × 440 86,5 460 | × × 440 86,5 600 |
Weight : | 14,4 | 27,1 | 32,8 |
COMMUNICATION INTERFACE |
|||
communication port | RS232 or USB |
||
Communication SLOT | SNMP card, relay card, etc. |
||
ENVIRONMENTAL CONDITIONS |
|||
Operating temperature | 0ºC ~ 40ºC |
||
Storage temperature | -25ºC ~ + 55ºC |
||
Humidity | 20 ~ 90% non-condensing |
||
Altitude | < 1500m (reduced when > 1500m) |
||
Noise | < 50dB (at 1 meter) |
||
safety regulations | IEC/EN 62040-1-1, IEC/EN 62040-2 |
||
* Reduction to 80% of the capacity when the output voltage is set to 200/208VAC |