INEO RT is a last generation double conversion On Line equipment, convertible. The INEO RT Range is designed with DSP control, with a high power factor, both at input and output (Cosine of Phi=1), wide input voltage range to achieve energy savings, and the ECOMODE system, which make it one of the most efficient on the market with >93,5%. It is the ideal equipment for server rooms, banks, industrial equipment, IT equipment, communication systems and other networking equipment, which demand superior protection.
– Multifunction LCD display – Hot swap battery – Wide input voltage range – Possibility of configuration in N+X arrangement redundant parallel – Online double conversion with DSP control – Low input current distortion – Green Concept design with a greater range of input voltage for energy saving – Emergency stop (EPO) – Adjustable battery voltage – Adjustable fan speed depending on the temperature – Common battery with UPS in parallel arrangement - Cold start – Selectable charging current – Galvanic isolation transformer module |
TYPICAL APPLICATIONS
– Automated doors – Great CPD |
FORMATConvertible in tower or rack format for mounting GENERATING SETFully compatible with electric generators |
ENTRANCES AND PORTS- USB port |
DATA SHEET
MODEL | INEO RT6000 | INEO RT10000 |
Capacity | 6KVA/6KW | 10KVA/10KW |
STARTERS | ||
Configuration | phase+N | |
Rated voltage | 208/220/230/240Vac | |
Voltage range | 120-276 Vac | |
Frequency range | 45~55Hz/54~66Hz | |
power factor | ≥0.99 @Rated voltage (100% load) | |
Bypass voltage range | Max voltage 220V:+25% (optional +10%, +15%, +20%) 230V: +20% (optional+10%, +15%) 240V: +15% (optional +10%)
Min. voltage -45% (optional -20%, -30%) |
|
Bypass frequency range | ±1% ~ ±2% ~ ±4% ~ ±5% ~ ±10% | |
ECHO range | Same as bypass | |
group entry | Admits | |
Harmonic distortion (THDi) | ≤ 3% (100% linear load); ≤ 5% (100% non-linear load); | |
PROJECTION | ||
Voltage range | 208/220/230/240VAC | |
power factor | 1 | |
voltage regulation | ± 1% | |
Frequency | Synchronized line mode with network
Battery mode 50 / 60Hz ±0.01Hz |
|
crest factor | 3:1 | |
THDv | ≤ 2% with linear load ≤ 5% with non-linear load | |
EFFICIENCY | ||
AC mode (full load) | >93.5% | |
BATTERY | ||
battery voltage | ±96/ ±108/ ±120Vdc | |
90% recharge time | 6-8 hours recharges to 90% of full charge | |
Charging Current (Built-in/Max.) | 1A (standard model); max current 10A (long autonomy model); (charging current can be modified in depending on the capacity of the installed batteries) |
|
SYSTEM CARACTERISTICS | ||
transfer time | Main on battery : 0; main to bypass: 9ms | |
Overload | Line mode Load ≤110%: for 60 min, ≤125%: for 10 min, ≤150%: for 1 min, ≤150%: for 200mn changes to bypass immediately Bypass mode 40A (Breaker) 63A (Breaker) |
|
Short circuit | maintains the system | |
Low battery | alarm and shutdown | |
Self diagnosis | At power on and software control | |
Low battery | Advanced battery management | |
Audible AND visual alarms | Line fault, low battery, overload, system fault | |
LED and LCD displays | Line mode, backup mode, ECO mode, bypass mode, low battery, bad battery, overload and fault | |
LCD display | Voltage input, frequency input, voltage output, frequency output, load percentage, battery voltage, indoor temperature, etc. |
|
communication interface | RS232, USB, parallel port, EPO and optional slot for SNMP card, contact card or Modbus card | |
ENVIRONMENTAL CONDITIONS | ||
Operating temperature | 0ºC ~ 40ºC | |
Storage Temperature | -25ºC ~ -55ºC | |
Humidity | 0 ~ 95% non-condensing | |
Altitude | <1500m | |
Noise level | <55db at 1 meter | |
STANDARDS | ||
SECURITY | IEC/EN 62040-1-, IEC/EN 62050-1 | |
EMC | IEC/EN 62040-2; IEC61000-4-2; IEC61000-4-3; IEC61000-4-4; IEC61000-4-5; IEC61000-4-6; IEC61000-4-8 | |
Battery Module | ||
Dimensions (WxHxD) | NW | GW |
443x131x720 | 12 | 15 |
Galvanic Isolation Transformer Module
MODEL | RT III 6K-XFR | RT III 10K-XFR |
Topology | Isolation, transformer by sections, sinusoidal | |
Home | ||
Frequency/Voltage | 1xxxx2W+G. 220/230VAC, 50/60Hz | |
Current (Max) | 24,5Amps (220/230Vac) | 40Amps (220/230Vac) |
Departure from | ||
Frequency/Voltage | 220 / 230Vac | |
Power (Max) | 6KVA/6KW | 10KVA/10KW |
Efficiency | >95% | |
Wave type | Sinusoidal | |
PHYSICAL | ||
Dimensions WxHxD (mm) | × × 440 86,5 685 | 443x131x677 |
Net weight / kg) | 13 + battery | 15 + battery |
Reviews